Fisher control valve with a volume booster and accessories mounted on the actuator

Positioners and instruments · Fisher

Fisher volume boosters and valve accessories

A control valve is an assembly: besides the positioner, these accessories decide its speed, its position signal and its failure action.

What are control valve accessories?

They are the instruments that, alongside the positioner, complete the control valve assembly: they move more air to shorten the stroke, report position, condition the supply air or impose a defined action if that supply fails.

The volume booster sits between the positioner and the actuator: when the signal changes sharply it quickly delivers a large volume of air and, when the change is slow, its integral bypass restriction leaves fine control to the positioner.

Fisher control valve with a volume booster and accessories mounted on the actuator
  • 2625 and VBL volume boosters
  • FIELDVUE 4400 position transmitter
  • 377 trip valves
  • 67C supply regulators

Models

Fisher valve accessory models

Manufacturer reference models for this type. Tell us the exact model or attach the nameplate: scope and availability are confirmed with each quotation.

Brand reference models per the manufacturer’s catalog. ITS quotes new valves and genuine parts to order; it does not publish stock or prices.

How it works

How they work

The booster takes the positioner output as its signal. While that signal changes slowly, air passes through the bypass restriction and steady-state accuracy is governed by the positioner. On a large, fast change, the booster opens its main port and moves air directly to or from the actuator. The bypass adjustment sets the balance between speed and stability.

The FIELDVUE 4400 position transmitter senses travel with no mechanical contact with the stem and provides a 4-20 mA signal with on/off indication; it is calibrated with local pushbuttons and communicates over HART. The 377 trip valve monitors supply pressure: when it falls below the trip point, it causes the actuator to fail up, fail down or lock in its last position, and it resets automatically when pressure recovers.

Constructions and trim

  • Volume boosters (Fisher 2625 and VBL)

    They increase the stroking speed of throttling valves and keep steady-state accuracy through their integral bypass restriction.

  • Position transmitter (FIELDVUE 4400)

    It senses the position of rotary or sliding-stem valves, vents and dampers and reports it to the control system; it is digital and linkage-less, with two solid-state limit switches.

  • Trip valves (Fisher 377)

    For applications that require a specific valve and actuator action when supply pressure falls below an adjustable point. A single valve covers the three failure modes.

  • Supply regulators (Fisher 67C)

    Direct-operated regulators, with or without a filter, that provide a constant, reduced pressure to pneumatic and electro-pneumatic instruments; the 67CFR includes a filter and internal relief.

Applications

Where they are used

  • Large actuators and fast loops that need short stroking times, such as anti-surge valves
  • Long supply lines, where the positioner alone does not move enough air
  • Remote position indication on control, safety and pressure relief valves
  • Double-acting piston actuators that require a defined action on loss of supply
  • Conditioning the air for each positioner, controller or transducer

Why it is chosen

  • More stroking speed without sacrificing positioner accuracy
  • A position signal independent of the positioner for the control system
  • A defined failure action on springless actuators as well
  • Accessories repairable with genuine kits and parts

Worth weighing

  • A badly adjusted booster makes the loop unstable: the bypass is adjusted with the complete assembly, on the bench or in service
  • Each accessory adds connections and potential leak points: install only those the service requires and document their configuration

ITS de Venezuela

What ITS does with valve accessories

We quote Fisher volume boosters, position transmitters, trip valves and supply regulators, with their genuine repair kits (diaphragms, seats and O-rings), and build the complete assembly on the actuator. In our Puerto Ordaz workshop and in the field we adjust the booster bypass, calibrate the transmitters and test the failure action; when the assembly carries a FIELDVUE instrument, we verify the response with ValveLink. Parts are managed through the Venezuela ↔ Orlando inventory. For a quotation, send the actuator model and size, the installed positioner, the supply pressure, the required stroking time and the failure action.

Quote parts or repair

Resources

Resources

The full category, the technical library and the manufacturer’s official documentation.

FAQ

Frequently asked questions

All frequently asked questions
When is a volume booster needed?

When the positioner alone does not move enough air to meet the stroking time: large actuators, long supply lines and fast loops. The booster delivers a large volume of air on sharp signal changes and, through its bypass restriction, leaves fine control to the positioner.

What is a position transmitter for if the valve already has a positioner?

So that the control system knows the actual valve position through an independent signal, useful for monitoring and interlocks. The FIELDVUE 4400 provides it with no mechanical contact with the stem, as a 4-20 mA signal with on/off indication.

Positioners and instruments

More positioners and instruments families

FIELDVUE digital valve controllers

The instrument that positions the valve and also diagnoses it: it evaluates the performance and health of the assembly without shutting down the process.

Pneumatic positioners

They deliver air to the actuator until stem or shaft position matches the set point, with a pneumatic or 4-20 mA signal.

Process controllers

They close the loop in the field: they measure the variable, compare it with the set point and send the corrective signal to the final element.

Level controllers

They measure and control liquid level, the interface between two liquids or density with a displacer sensor, in pneumatic, electric or digital versions.

I/P transducers

They convert the 4-20 mA electrical signal into a proportional pneumatic pressure: the link between the electronic loop and the air-operated valve.

Fisher OEM Parts is the online catalog of ACD America Corp., our parent company. It opens in a new tab.

Need volume boosters and valve accessories, or repair for yours?

Send the model, the part number or the process data. We reply with availability, lead time and delivery terms.

Product bulletin

Loading the bulletin…

  1. 1Details
  2. 2Verification
  3. 3Request

Message us on WhatsApp

We verify your details and connect you with the specialist for your region.

Receive the phone code by